Permit: T06CM05780

Parcel: 141185710

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The inspector was unable to locate the job.| 945*
CALLED APN BUILDERS, LEFT MESSAGE WITH
INSPECTORS PH#, NO RETURN CALL - COULD NOT LOCATE
5:20 PM RECALL INSPECTION
09/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL DISCONNECT FOR INSTANT HOT
2) INSTALL EXTENSIONS ON BOXES ? MORE THAN 1/4"
3) INSTALL BUBBLE COVER ON RECEPTS EXPOSED TO WEATHER
4) CANNOT USE SHEET METAL SCREW FOR GROUND CONNECTIONS
5) MARK DISCONNECTS FOR LOAD SERVED
6) MARK SERVICE DISCONNECT
7) MARK ASSCESSORIES AT HEAT PUMP
8) EMERGENCY LIGHTING NOT PER PLAN-NEED REVISION AND APPROVAL
9) LIGHT SWITCHING NOT PER PLAN-NEED REVISION AND APPROVAL
10) NEED PANEL SCHEDULE