Permit: T06CM05780

Parcel: 141185710

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/05/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
09/14/2007 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
09/12/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. POST BOND FOR POWER
2. NEED TO BOND NIPPLE BETWEEN CT CAN & 400 AMP DISCONNECT NEC 250.92 & 250.102
3. DISCONNECT MOUNTED TO HIGH 6'7" MAX TO HANDLE
NEC 404.8
4. REMOVE PAINT AT BUILDING STEEL GROUND CONNECTORS NEC 250.12