Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 09/14/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 09/12/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POST BOND FOR POWER 2. NEED TO BOND NIPPLE BETWEEN CT CAN & 400 AMP DISCONNECT NEC 250.92 & 250.102 3. DISCONNECT MOUNTED TO HIGH 6'7" MAX TO HANDLE NEC 404.8 4. REMOVE PAINT AT BUILDING STEEL GROUND CONNECTORS NEC 250.12 |