Permit: T06CM05780

Parcel: 141185710

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
11/05/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
08/23/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1 1/4" PVC TO PUMP LIFT STATION
08/08/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 1 - 4" PVC FROM TEP X-FORMER TO SES
2. APPROVED PLANS NEED TO BE AVAILABLE FOR ALL INSPECTIONS
3. CANNOT USE CHASE NIPPLES AND THREADED COUPLING FOR CONNECTION OF CT CAN TO MAIN DISCONNECT
4. INSTALL WARNING RIBBON ABOVE SERVICE ENTRANCE CONDUCTORS PER PLAN & NEC 300.5 WILL CHECK AT SERVICE INSPECTION.
08/03/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO HAVE APPROVED SET OF DRAWINGS ON SITE AND AVAILABLE TO INSPECTOR FOR INSPECTIONS
2. CANNOT USE WAX CORE FOR SECONDARY CONDUCTOR FROM TEP TRANSFORMER TO SES. NEED TO USE RECOGNIZED WIRING METHOD OF CHAPTER 3 OF NEC
ALSO, NEEDS TO BE LISTED PRODUCT
3. NIPPLE BETWEEN CT CAN & DISCONNECT NEEDS TO BE BONDED PER NEC 250.92
4. DISCONNECT SWITCHES AT SERVICE LOCATION ARE HIGHER THAN 6'7" -- NEC 404.8
5. NOT A COMPLETE SERVICE INSPECTION
08/02/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELLED BY ELECTRICAL CONTRACTOR