Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM05760
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 02/08/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USED 8D NAILS IN HANGERS AT GARAGE LEDGER 8D NAIL ARE NOT ALLOWED IN ANY LOAD BEARING HANGER THE MINIMUM YOU CAN USE AT THAT LEDGER IS 10D COMMON THAT IS A DERATED LOAD CAPACITY. PLEASE USE 16D COMMON HANGER NAIL OR 8D SINKERS, HOLE HAS BEE MADE BY 8D 2) USE TWO NAILS MINIMUM AT TOP/BOTTOM PLATES EACH WIND BRACE 3) TRUSS DRAWING LAYOUT DOES NOT REFLECT WHAT WAS INSTALLED 4) SOME P.A.'S HAVE INCORRECT NAIL SIZE 5) OSB JOINT NOT NAILED FRONT SMALL HIP, ALSO OSB TURNED OPPOSITE STRENGTH ORIENTATION FRONT BLK FROM BELOW 6) C02 & C03 TRUSSES BEAR ON BOTH SIDE OF TOWER ENTRY, RAT RUNS MISSING ON THESE TRUSSES 7) NAIL SHEAR TRANSFER PANELS TO ROOF 8) NAIL IN 3" ABS AT GARAGE SHEAR |