Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM05759
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR TILES MECHANICAL ONLY |
|
10/08/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE SADDLES PER HVAC NOTES 2. PROVIDE 1.5 RADIUS ON FLEX BENDS PER DETAIL 10 3. PROVIDE FLEX DUCT SUPPORT SUFFICIENT TO AVOID SAGGING PER I.M.C 4. PROVIDE FLEX CONNECTORS PER DETAIL 2 |