Permit: T06CM05759

Parcel: 13824023H


Addresses:

2011 W VALENCIA RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM05759

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR TILES
MECHANICAL ONLY
10/08/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE SADDLES PER HVAC NOTES
2. PROVIDE 1.5 RADIUS ON FLEX BENDS PER DETAIL 10
3. PROVIDE FLEX DUCT SUPPORT SUFFICIENT TO AVOID SAGGING PER I.M.C
4. PROVIDE FLEX CONNECTORS PER DETAIL 2