Permit: T06CM05759

Parcel: 13824023H


Addresses:

2011 W VALENCIA RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/04/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MOTORS FOR HYDRAULIC POWER PACKS NOT LISTED
2. PROVIDE 3RD PARTY EVALUATION FOR APPROVAL (NRTL) LISTING.
3. OK TCO SUBJECT TO OTHER INSPECTORS
11/04/2008 ELECTRIC - FINAL Partial Approval
10/31/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY LISTINGS FOR EQUIPMENT, COMPRESSORS
2. LABEL DISCONNECT/MORTAR STARTERS
3. BOND BUSHING AT CONCENTRICS 250.97
4. MAINTAIN WORKING CLEARANCES & DEDICATED
SPACE 110.26
5. INSTA-HOTS NOT CORD & PLUG

CONTRACTOR CANCELED REST OF INSPECTION