Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 07/27/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE MAIN SERVICE PANEL TO WALL 2) IDENTIFY 60 AMP BREAKER IN PANEL 3) SEAL KNOCKOUTS IN PANEL 4) CLEAN UP AND SECURE PVC CONDUIT TO PANEL 5) INSTALL BATTERY OPERATED SMOKIES IN ALL BEDROOMS AND HALLWAYS 6) UNABLE TO LOCATE SUB PANEL/BASE BOARD HEATER AND A/C COOLING MUST BE ON SEPERATE CIRCUIT 7) INSTALL LIGHT FIXTURES ALL EXTERIOR DOORS 8) ARC FAULT ALL OUTLETS IN ADDITION BEDROOM 9) RECEPTACLE AT ENTRY DOOR TESTS OPEN GROUND ADDITION 10) SECURE ROMEX TO FAN 8" FROM BOX 11) EXPOSE BOTTOM PLATES |
|
| 04/17/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE LICENSED ELECTRICIAN CERTIFY IN WRITTING THAT ALL ELECTRICAL WORK DONE IN BEDROOM MEETS CURRENT IRC CODE 2) PROVIDE TEST HOLE AT BRICK VENEER FOOTING UNDER 2 X 2 WINDOW |