Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM05746
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
03/11/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) RECEIVED LETTER OF TORQUE |
|
03/03/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. LABELING CANNOT BE CHANGED IN THE FIELD WITHOUT A THIRD PARTY INSPECTION 2. PLEASE HAVE GEAR OPENED FOR INSPECTION |
|
02/11/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. POST BOND FOR TEMP POWER TO TEST 2. PROVIDE LETTER OF TORQUE 3. SECURE SWITCHGEAR TO CONCRETE 4. INSTALL BELL ENDS ON PVC 5. PLAN CALLS FOR GEAR TO BE RATED 100KAIC 6. EXTEND GEC BY EXOTHERMIC WELD OR BY COMPRESSOR |