Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
12/16/2009 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) INSTALL ANTI-CORROSION PASTE ON ALUMINUM FEEDS 2) EXPOSE GROUNDING SYSTEM OR INSTALL 2 DRIVEN RODS |
|
08/19/2009 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |