Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
12/06/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
12/01/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CABLE #10 STILL HAS 13 DAMAGED SPOTS THAT HAVE HAD NO REPAIR
2) CABLE 23 DAMAGED WITHOUT REPAIR
3) AN EXCESS OF 40 REPAIRS HAVE BEEN MADE TO CABLE DAMAGE
4) ALL CABLE DAMAGE REPAIRS APPEAR TO NOT COMPLY WITH POST TENSION INSTITUTE STANDARDS. YOU MUST PROVIDE APPROVED WRITTEN GUIDE LINES FOR CABLE DAMAGE AND REPAIR AT ALL POST TENSION INSPECTIONS
5) YOU MUST PROVIDE A NEW SPECIAL INSPECTION REPORT SPECIFYING ALL DAMAGE LOCATIONS ON EACH CABLE AND NOT REPAIR SPECIAL INSPECTION REPORT MUST BE DATED 1 DEC 06 OR LATER
11/30/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CABLE SHEATHING DAMGED THROUGHOUT. REPAIR PER POST TENSION INSTITUTE STANDARDS AND PROVIDE SPECIAL INSPECTION REPORT