Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM05715
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/20/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/16/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAULK ALL PENETRATIONS 2) TIGHTEN DOWN ALL H.D. NUTS 3) NEED DWV TEST 4) PROTECT STAT WIRE AT KITCHEN PANTRY 5) DAMAGED TRUSS JOINT 2ND FLOOR MIDDLE BEDROOM 5) SW9 SHEARWALL AT STAIR 1ST FLOOR 3/4 DIAMETER ABS 24" ON CENTER 6) NAIL 2ND FLOOR PLATES TO FLOOR 6" ON CENTER WITH 16DS BETWEEN LARGE ? 7) INSTALL ALL A.B.'S 1ST FLOOR, WRITTEN ON CONCRETE, EXCEPT 3/4 DIAMETER BOLTS AT STAIR |