Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05699
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SHEETMETAL SCREWS NOT ALLOWED FOR BONDING 250.8 2. BONDING JUMPER PER 250.122 3. MAINTAIN WORKING CLEARANCE 110.26 |
|
03/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NO INSPECTIONS HAVE BEEN MADE IN ROOM 106 & 107 2. ATTACH FIXTURES TO GRID 410.16 3. A SUPPORT WIRE IS NEEDED FOR EXIT SIGNS 4. PLEASE REMOVE ABANDONED FIXTURE WHIP 5. VERIFY IF EM & EXIT LIGHTING IS AS PER 700.12 6. ROOF DISCONNECT HAS MULTIPLE TERMINATION UNDER LUG 7. 480V FEED ACROSS ROOF NOT ON PLANS PLEASE REVISE PLANS OR REMOVE IF LEFT MAKE SAFE 8. MDP ENERGIZED WITHOUT INSPECTIONS PLEASE HAVE ELECTRICIAN PRESENT & DE-ENERGIZE |
|
12/28/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
12/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING OR BONDING 250.8 2. FIXTURES TO BE ATTACHED TO GRID 410.16 3. SUPPORT EXISTING VDV CABELING 725.3 & 6 4. SUPPORT BOXES & CONDUITS MOVED DURING DEMO PER CODES. 5. FILL UNUSED OPENINGS IN BOXES 6. VERIFY PAPERWORK FOR ASSEMBLY LISTING DO NOT USE EQUIPMENT |