Permit: T06CM05693

Parcel: 10707005K


Addresses:

1375 W GLENN ST 01


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T06CM05693

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/14/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
03/16/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNDERGROUND HYDRO AND DRAIN OUT TO PAD
PRESSURE TESTS OK 100 + AND 5 +
02/11/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNDERGROUND DRAIN PIPING PRESSURE TEST OK, OK FOR BURIAL
02/05/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CONFIRMED LISTED PIPE FOR HYDRONIC & DRAIN PIPING
2. OK TO INSTALL AND INSULATE DRAIN PIPE
3. PROVIDE 10' HEAD OR 5 PSI TEST
4. PROVIDE MIN. 100 PSI HYDROSTATIC TEST ON
HYDRONIC PIPING
01/30/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT OK TO PROCEED