Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05692
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
06/14/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXCEEDING MAX FUSE SIZE FOR REFRIDGERATOR CONDENSING UNIT 2) FUSE CLIPS NOT MAKING GOOD CONTACT ON ROOF TOP A/C UNITS CHECK ALL UNITS 3) INSTALL ? RELIEF ON CORD TO DISHWASHER 4) ATTACH PANEL SCHEDULE TO PANELS 5) EMERGENCY LIGHTING NOT PER DRAWING |
|
06/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |