Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM05687
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
02/20/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
02/16/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* HP 13, 14 & 15 MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. HP 17 & 18 PROVIDE CONDENSATE DRAIN LINE TO UNIT. ALL CONDENSATE DRAINS FROM THIS SUITE MUST TERMINATE INTO THIS SUITE. RE-ROUTE DRAIN LINES FROM HP 13, 14 & 15 |