Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM05687

Parcel: 133243720

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM05687

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/20/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
02/16/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
HP 13, 14 & 15 MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY.

HP 17 & 18 PROVIDE CONDENSATE DRAIN LINE TO UNIT.

ALL CONDENSATE DRAINS FROM THIS SUITE MUST TERMINATE INTO THIS SUITE. RE-ROUTE DRAIN LINES FROM HP 13, 14 & 15