Permit: T06CM05687

Parcel: 133243720

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05687

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/20/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF:
1. NEED MAINTENANCE RECEPTACLE 210.63
2. COVERS TO BE AS PER 406.8
3. TIGHTEN LOOSE SEAL TITE FITTINGS
4. REMOVE TEMP OUTLET
02/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*