Permit: T06CM05681

Parcel: 141313390

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM05681

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/01/2007 EXT METAL CLIPS/EXT SHEATHING Denied 1) FROM LAST INSPECTION LOAD BEARING HANGER NAILS START AT 10D COMMON 8D ARE NOT APPROVED FOR ANY LOAD BEARING HANGER MINIMUM FOR THESE HANGERS ARE .148 DIA. BECAUSE THERE IS NOT THAT MUCH WEIGHT. PLEASE SEE SIMPSON REFERENCE BOOK
02/28/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FROM LAST INSPECTION, YOU CANNOT USE 8D .131 DIAMETER NAILS IN HANGERS LOAD BEARING. SIMPSON OR OTHER METAL HANGER SUPPLIERS, REQUIRE NAILS USED TO BE COMMON NAILS, NOT BOX NAILS. .148 DIAMETER = 10D COMMON AND .131 DIAMETER = 8D NAIL
2) CANNOT USE 8D NAILS IN LOAD BEARING HANGERS, 8D TECO NAILS ARE FOR H2.5 AND A3.5 CLIPS ECT. NOT HANGERS
3) NEED THE CARPENTER HERE TO REMOVE A BLK THAT COVER HANGER FLANGE, SPOT CHECK
02/23/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval OK TO WRAP WALLS AND DRY IN ROOF
DON'T LOAD TILE UNTIL, SPOT CHECK HANGER NAILS. 10S ARE OK, NO EIGHTS
02/22/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval 1) FRONT ENTRY TOWER BEARING PTS NOT SHIMED
2) 3 PT BEARING MAIN HOUSE NOT SHIMED
3) SMALL PIECES OF OSB TURNED WRONG WAY ON ROOF
4) 16A/SD3 NEED BLOCKS FOR ROOF LOAD 2 X 4 16" ON CENTER
5) ALL P.A. STRAPS THAT HAVE .131 DIAMETER NAILS MUST CHANGE TO .148 MIN
6) P 8 NAILS USED IN HANGERS USE .148