Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2007 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 08/15/2007 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* PVC IN YARD OK USE CLEAN FILL |
|
| 07/23/2007 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEC 316.1.1.4 & 301.1.2.4.2 INSTALLATION STANDARD #8 ALSO, SEE MANUFACTURES INSTRUCTIONS. WHEN PIPE LABELING IS VISIBLE INTO JOINT I CANNOT BE SURE THAT PRIMER WAS USED. 2003 UPC SEC 316.1.6 ALSO, SEE SEC 609.1 PIPING SHALL BE SIZED PER APPROVED SITE PLAN |
|
| 07/18/2007 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* - BELOW GRADE PIPING SHALL BE PROPERLY SUPPORTED - CHANGES OF DIRECTION SHALL BE MADE W/FITTINGS - PIPING SHALL NOT BE STRAINED - TRACER WIRE SHALL BE SECURED TO PIPING AT 8' - USE WEATHER RESISTANT WIRE NUT TO REPAIR TRACER WIRE - RP AND LINE SIZE FROM METER TO PROP LINE NOT SIZED PER PLUMBING PLAN - SP1 SITE UTILITY PLAN DOES NOT HAVE PLUMBING PLAN REVIEW STAMP - YOU HAVE BEEN WARNED PREVIOUSLY THAT CONTINUED DENIED INSPECTIONS MAY RESULT IN RE-INSPECTION FEE |
|
| 07/17/2007 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* USE FITTINGS TO OFFSET - SECURE WIRE AND INSTALL 1 1/4" RP AND WATER PIPE TO METER - OK TO COVER FROM BUILDING BACK 40' |