Permit: T06CM05679

Parcel: 12218258C


Addresses:

3731 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
08/31/2007 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
08/15/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
PVC IN YARD OK
USE CLEAN FILL
07/23/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEC 316.1.1.4 & 301.1.2.4.2 INSTALLATION STANDARD #8
ALSO, SEE MANUFACTURES INSTRUCTIONS.
WHEN PIPE LABELING IS VISIBLE INTO JOINT I CANNOT BE SURE THAT PRIMER WAS USED.
2003 UPC SEC 316.1.6 ALSO, SEE SEC 609.1
PIPING SHALL BE SIZED PER APPROVED SITE PLAN
07/18/2007 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- BELOW GRADE PIPING SHALL BE PROPERLY SUPPORTED
- CHANGES OF DIRECTION SHALL BE MADE W/FITTINGS
- PIPING SHALL NOT BE STRAINED
- TRACER WIRE SHALL BE SECURED TO PIPING AT 8'
- USE WEATHER RESISTANT WIRE NUT TO REPAIR TRACER WIRE
- RP AND LINE SIZE FROM METER TO PROP LINE NOT SIZED PER PLUMBING PLAN
- SP1 SITE UTILITY PLAN DOES NOT HAVE PLUMBING PLAN REVIEW STAMP
- YOU HAVE BEEN WARNED PREVIOUSLY THAT CONTINUED DENIED INSPECTIONS MAY RESULT IN RE-INSPECTION FEE
07/17/2007 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
USE FITTINGS TO OFFSET - SECURE WIRE AND INSTALL 1 1/4" RP AND WATER PIPE TO METER - OK TO COVER FROM BUILDING BACK 40'