Permit: T06CM05679

Parcel: 12218258C


Addresses:

3731 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/17/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/16/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SAFETY STRAPS NEEDED,
PSI ON WATER AND SUPPORTS ON COPPER
DWV TEST OK
07/10/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. HAVE 03037 ROOF DRAINS ADDED TO YOUR PERMIT
AND CALL THIS INSPECTION USING THE PROPER CODE.
2. PROVIDE INSPECTION HISTORY FOR UNDER SLAB COPPER
COPPER TO BE PROTECTED PASSING THRU MASONRY
COPPER NOT INSTALLED PER PLAN NO REDLINES ON SITE
ABS NOT INSTALLED PER PLAN
NO PROVISION MADE FOR INSULATING HOT & RETURN PIPING
SEVEN FLANGES TO THE FLOOR
TIE-WIRE NOT APPROVED STRAP
SUPPORT COPPER PER TABLE 3-2 2003 UPC
ALL WATER BEING USED ON THIS SITE TO HAVE BACKFLOW PROTECTION
CONTINUED "NOT READY'S" WILL RESULT IN A REINSPECTION FEE.