Permit: T06CM05679

Parcel: 12218258C


Addresses:

3731 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/17/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. RADIANT HEATERS NOT LISTED/IDENTIFIED 424.28
2. FINISH CORRECTIONS FROM PREVIOUS INSPECTION #1, 5, 8
10/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN
ALSO, NEEDS TO COMPLY WITH NEC 700.12 - CHECK ALL AND CORRECT AS NEEDED
2. ON ROOFTOP - DISCONNECTS FOR "EC1", "HP3" AND "HP1" TO HAVE PROPER FRONT WORKING CLEARANCE
(30" WIDE & 36" DEEP) SEE NEC 110.26
3. NEED BOX EXTENDERS WHERE BOXES SIT BACK MORE THAN 1/4" FROM WALL OR ARE NOT FLUSH WHERE COMBUSTIBLE CHECK FOR BURIED RECEPTACLE @ SALES
4. CHECK FOR PROPER OPERATION/ADJUSTMENT OF OCCUPANCY SENSORS
5. LOW VOLTAGE WIRING NOT COMPLETE
6. NEED FLOOR RECEPTACLE
7. AIM EMERGENCY LIGHTING SO IT IS EFFECTIVE
8. PROVIDE DATA PLATE/MANUAL/LISTING INFORMATION FOR RADIANT HEATERS

PARTIAL INSPECTION ONLY
9. PROVIDE PHYSICAL PROTECTION FOR SERVICE
NEC 110.26 A2