Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. RADIANT HEATERS NOT LISTED/IDENTIFIED 424.28 2. FINISH CORRECTIONS FROM PREVIOUS INSPECTION #1, 5, 8 |
|
| 10/05/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN ALSO, NEEDS TO COMPLY WITH NEC 700.12 - CHECK ALL AND CORRECT AS NEEDED 2. ON ROOFTOP - DISCONNECTS FOR "EC1", "HP3" AND "HP1" TO HAVE PROPER FRONT WORKING CLEARANCE (30" WIDE & 36" DEEP) SEE NEC 110.26 3. NEED BOX EXTENDERS WHERE BOXES SIT BACK MORE THAN 1/4" FROM WALL OR ARE NOT FLUSH WHERE COMBUSTIBLE CHECK FOR BURIED RECEPTACLE @ SALES 4. CHECK FOR PROPER OPERATION/ADJUSTMENT OF OCCUPANCY SENSORS 5. LOW VOLTAGE WIRING NOT COMPLETE 6. NEED FLOOR RECEPTACLE 7. AIM EMERGENCY LIGHTING SO IT IS EFFECTIVE 8. PROVIDE DATA PLATE/MANUAL/LISTING INFORMATION FOR RADIANT HEATERS PARTIAL INSPECTION ONLY 9. PROVIDE PHYSICAL PROTECTION FOR SERVICE NEC 110.26 A2 |