Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/18/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CHARLIE 349-5029 LETTER OF TORQUE RECEIVED TODAY |
|
| 09/13/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* FIXTURE CLIPS OK TO SUPPORT FIXTURE IN ADDITION TO SUPPORTS TO STRUCTURE FOR SEISMIC WIRES |
|
| 09/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2X4'S & CONDUIT RUNS OK CONDUCTOR CONNECTION TO LUGS 1. SUPPORT VDV CABELING AS PER 725.6 & 800.6 & 300.11 2. SUPPORT CONDUITS BELOW PANELS TO PREVENT BREAKAGE OF PVC CONDUITS ABOVE FINISHED FLOOR 3. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS NO MECHANICAL SPLICES -- 250.64 4. PLEASE PROVIDE A LETTER ON COMPANY LETTERHEAD VERIFYING TORQUE OF EQUIPMENT & CONDUCTORS 5. FOR POWER TO INTERIOR: A BOND NEEDS TO BE POSTED, PLUG, SWITCH, AND OR PLATE DEVICES 8' AND BELOW, CLOSE ALL WALLS, ADD 02062 TO PERMIT. |
|
| 07/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK LIGHTS IN OUTDOOR SOFFITS |
|
| 07/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE ADDITIONAL BACK SUPPORT FOR RECEPTACLE BOXES AS NEEDED 2. STUB YOUR 3/0 CU WATER BOND UP WALL BEFORE COVER OK INTERIOR ELECTRICAL WALL COVER AFTER CORRECTIONS. |
|
| 04/23/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK TO COVER PANELS -- "L" "PA" "P" "RH" RACEWAYS UNDER SLAB |