Permit: T06CM05679

Parcel: 12218258C


Addresses:

3731 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/05/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CHARLIE 349-5029
LETTER OF TORQUE RECEIVED TODAY
09/13/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
FIXTURE CLIPS OK TO SUPPORT FIXTURE IN ADDITION TO SUPPORTS TO STRUCTURE FOR SEISMIC WIRES
09/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2X4'S & CONDUIT RUNS
OK CONDUCTOR CONNECTION TO LUGS

1. SUPPORT VDV CABELING AS PER 725.6 & 800.6 & 300.11
2. SUPPORT CONDUITS BELOW PANELS TO PREVENT BREAKAGE OF PVC CONDUITS ABOVE FINISHED FLOOR
3. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS NO MECHANICAL SPLICES -- 250.64
4. PLEASE PROVIDE A LETTER ON COMPANY LETTERHEAD VERIFYING TORQUE OF EQUIPMENT & CONDUCTORS
5. FOR POWER TO INTERIOR: A BOND NEEDS TO BE POSTED, PLUG, SWITCH, AND OR PLATE DEVICES 8' AND BELOW, CLOSE ALL WALLS, ADD 02062 TO PERMIT.
07/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK LIGHTS IN OUTDOOR SOFFITS
07/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE ADDITIONAL BACK SUPPORT FOR RECEPTACLE BOXES AS NEEDED
2. STUB YOUR 3/0 CU WATER BOND UP WALL BEFORE COVER

OK INTERIOR ELECTRICAL WALL COVER AFTER CORRECTIONS.
04/23/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK TO COVER PANELS -- "L" "PA" "P" "RH" RACEWAYS UNDER SLAB