Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T06CM05677
Inspection Description - SITE - SEWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2008 | SITE - SEWER | Approved | IVRS - Inspection :* FOR FINAL WILL NEED TO SEE EXTERIOR CLEANOUTS TO GRADE WITH CORRECT TERMINATION OF BACKWATER VALVE ACCESS PER DETAIL 3/P1.4 |
|
10/08/2008 | SITE - SEWER | Partial Approval | VENT FOR BACKWATER VALVE THRU ROOF OK 1. PROVIDE ADDITIONAL SUPPORT ROOM 133 OVERHEAD |
|
08/20/2008 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 4" VENT FOR SEWER BECAUSE OF BACKWATER VALVE FROM SEWER BACK TO NORTHEAST CORNER OF ROOM 133 5' ABOVE FINISH FLOOR WATER TEST OK 1. PLEASE SEE DETAIL 3/P1.4 FOR CORRECT INSTALL OF BACKWATER VALVE WITH CORRECT EXTENDABLE ARM AND GRADE COLLARS |
|
12/18/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* VENT FROM INTERCEPTOR BACK TO 3' AFF AT BLD OK |
|
12/14/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 4" FROM BLD THRU INTERCEPTOR TO NEW SITE SEWER CONNECTION WITH 2" VENT WATER TEST OK 2" VENT REQUIRES LONG RADIUS FITTINGS. |
|
12/11/2007 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
12/05/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* WATER TEST PER REDLINE ON SITE WITH BACK WATER VALVE INSTALLED FOR ALL 3-HCS STUBS 1. SHALL PROVIDE PROOF OF NEED FOR ALL BUILDINGS USING SAME BACKWATER VALVE. THIS VALVE TO BE MADE ACCESSIBLE PROPERLY 2. SHALL MAKE CONNECTION TO SERVICE BLD & SEPARATOR & TEST |
|
12/04/2007 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
12/03/2007 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* |