Permit: T06CM05677

Parcel: 130140230


Addresses:

4220 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Date Description Inspector Results Comments
10/08/2008 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
10/03/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
- NORTHWEST 6" RD AND OFRD TEST OK
- REPAIR LEAK AT NORTHEAST LOCATION IN
SHOWROOM & RETEST
- NOTE: SHUT OFF DRINKING FOUNTAIN IN ALCOVE 171 UNTIL YOU HAVE A CLEAN BACTERIA REPORT AFTER CHLORINE OF SYSTEM.
10/02/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
6" RD & OFRD WATER TEST NORTHEAST CORNER OK
06/27/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
6" RD & OFRD AT SOUTHWEST B.5 & C.5
WATER TEST OK PER INITIAL P1.2
06/26/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
6" RD & OFRD AT SOUTHEAST CORNER OF CUSTOMER WAITING AREA WATER TEST OK
06/25/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
06/19/2008 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
- WATER TEST 6" RD ONLY AT SOUTHEAST CORNER OF
SALES WATER TEST OK
- 4" RD & OFRD SOUTHEAST CORNER OF CANOPY
WATER TEST OK

1. PROVIDE LEAD FLASHING, UNDER DECK CLAMPS AND CORRECT SUPPORT ON PIPING FOR HORIZONTAL PIPING