Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05677
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF INSPECTION 1. TIGHTEN LOOSE FITTINGS 2. INSTALL BONDING BUSHINGS AROUND CONCENTRICS SALES BUILDING 1. OUTDOOR EM LIGHTS NOT WORKING 2. SOME INDOOR EM LIGHTS NOT WORKING 3. WILL NEED TO CHECK ALL OUTDOOR LIGHTING WHEN COMPLETE |
|
11/20/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. RECEPT. MISWIRED. RECEPT TO BE FLUSH OR EXTEND PAST PLATES. NO MORE THAN 1/8" GAP AROUND MUD RINGS 2. MISSING RECEPT PLATE. MISSING SWITCH PLATES. 3. WIRES HANGING OUT OF WALLS (MISSING RECEPT) ELECTRICIAN WORKING IN CEILING 4. NOT ALL LAMPS LIT IN FIXTURES 5. INSTALL EXTENSION ON RECEPT IN PLYWOOD & TIE WALLS/SWITCHES ALSO 6. RECEPTS NO POWER 7. LIGHTS NOT WORKING 8. MISSING FLOOR RECEPTS 9. MISSING EXITS & EM LIGHTS OUTDOOR EM LIGHTS TO BE LISTED FOR WET LOCATION WHERE EXPOSED 10. EM LIGHTS NOT WORKING 11. NEED COMPLETE SET OF APPROVED DRAWINGS 12. INSTALL DISCONNECTING MEANS FOR HW RECIRC PUMP 13. NOT A COMPLETE INSPECTION. GO THRU ENTIRE JOB. |
|
10/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK PARTIAL FINAL FOR PARTS STORAGE FIRST FLOOR AND MEZZANINE. NO OFFICE OR OTHER ROOMS TO BE OCCUPIED 2. OK HARD LIDS RMS. 138, 139, 141, 144, 145 |
|
04/16/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SOME EM LIGHTING IN SHOP BUILDING NOT OPERATING 2. RECEIVED LETTER OF TORQUE |
|
04/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK MAKE UP @ POLE LIGHTS 2. OK DISCONNECTS FOR LIFTS & EXHAUST FANS |