Permit: T06CM05677

Parcel: 130140230


Addresses:

4220 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05677

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/12/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PONY WALLS @ 2 FRONT OFFICES IN SHOWROOM AREA
11/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILING 104 & 105
10/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILINGS EXCEPT RMS. 104 & 105
AND SMALL HALLWAY EAST END OF SALES FLOOR
10/24/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE TILES FOR CEILING INSPECTION
2. ATTACH FIXTURES TO GRID
3. INSTALL SEISMIC WIRES ON ALL FIXTURES
10/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK OUTDOOR LIGHTING IN SOFFITS EAST & WEST OF SALES FLOOR

WAITING & SERVICE WRITERS & PARTS & RESTROOMS
1. ONE EM LIGHT NOT WORKING
CHECK EXITS CANNOT TELL IF WORKING
2. REPLACE BAD GFI RECEPT.
3. DO NOT OCCUPY AREAS WITHOUT INSPECTION FIRST
09/29/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PONY WALLS SHOW ROOM
2. OK OUTSIDE WALLS SHOW ROOM
3. OK CURTAIN WALLS SHOW ROOM
4. OK HARD LIDS RMS. 140, 142, 143, 148
09/23/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK AREA OFFICES SOUTH OF CORRIDOR PARTS AREA
09/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. NO PERMISSION WAS GIVEN TO ONE SIDE ANY WALLS.
NEXT TIME SHEETROCK WILL BE REMOVED BEFORE ANY INSPECTIONS WILL BE DONE & REFEE WILL BE GIVEN
2. OK WALLS 147, 118-128, 146, 148
09/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS 129, 130, 131, 132, 133
08/27/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. LIGHT FIXTURES TO BE ATTACHED TO GRID
2. CLOSE OPEN JUNCTION BOXES
3. INSTALL ALL LOW VOLTAGE CABLING
4. FINISH ALL CEILING WORK
5. OK U.G TO 2 POLE LIGHTS EAST OF DRIVE UP
6. LP2A HAS 225 AMP. BUS BEING FED BY 250 AMP BREAKER
7. OK TO ENERGIZE PANELS 2ND FLOOR ELECTRIC CLOSET
07/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SOFFIT MAIN AREA
2. OK COFFEE BAR AREA WALLS
3. OK WALLS END OFFICE EAST SIDE
4. OK WALLS TOOL STORAGE
06/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SOFFIT @ SERVICE DRIVE
2. OK U.G TO FLOOR BOX @ CASHIER DESK
3. OK WALLS BREAK RM. TECH BATHROOM, WOMENS BATHROOM, LOCKER
4. OK HARD LIDS TECH BATHROOM, LOCKER, WOMENS BATHROOM
06/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK HARD LID SERVICE DRIVE
2. OK SOFFIT @ VENDING
3. OK WALLS RMS. 166 AND HALL OUTSIDE VENDING & RM 137
06/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS, ROOM #181
06/12/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RMS 135-137, 149-156, 159, 164-170
04/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SERVICE INSPECTION ONLY
2. PROVIDE LETTER OF TORQUE
03/28/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. POST BOND FOR TEMP POWER
2. PROVIDE LETTER OF TORQUE
3. BONDING JUMPERS NOT SIZED PROPERLY ON SERVICE RACEWAY NEC 250.102
4. INSTALL SYSTEM BONDING JUMPER @ XFMR NEC 250.30