Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05677
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/12/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PONY WALLS @ 2 FRONT OFFICES IN SHOWROOM AREA |
|
11/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILING 104 & 105 |
|
10/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILINGS EXCEPT RMS. 104 & 105 AND SMALL HALLWAY EAST END OF SALES FLOOR |
|
10/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE TILES FOR CEILING INSPECTION 2. ATTACH FIXTURES TO GRID 3. INSTALL SEISMIC WIRES ON ALL FIXTURES |
|
10/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK OUTDOOR LIGHTING IN SOFFITS EAST & WEST OF SALES FLOOR WAITING & SERVICE WRITERS & PARTS & RESTROOMS 1. ONE EM LIGHT NOT WORKING CHECK EXITS CANNOT TELL IF WORKING 2. REPLACE BAD GFI RECEPT. 3. DO NOT OCCUPY AREAS WITHOUT INSPECTION FIRST |
|
09/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PONY WALLS SHOW ROOM 2. OK OUTSIDE WALLS SHOW ROOM 3. OK CURTAIN WALLS SHOW ROOM 4. OK HARD LIDS RMS. 140, 142, 143, 148 |
|
09/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK AREA OFFICES SOUTH OF CORRIDOR PARTS AREA |
|
09/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NO PERMISSION WAS GIVEN TO ONE SIDE ANY WALLS. NEXT TIME SHEETROCK WILL BE REMOVED BEFORE ANY INSPECTIONS WILL BE DONE & REFEE WILL BE GIVEN 2. OK WALLS 147, 118-128, 146, 148 |
|
09/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS 129, 130, 131, 132, 133 |
|
08/27/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. LIGHT FIXTURES TO BE ATTACHED TO GRID 2. CLOSE OPEN JUNCTION BOXES 3. INSTALL ALL LOW VOLTAGE CABLING 4. FINISH ALL CEILING WORK 5. OK U.G TO 2 POLE LIGHTS EAST OF DRIVE UP 6. LP2A HAS 225 AMP. BUS BEING FED BY 250 AMP BREAKER 7. OK TO ENERGIZE PANELS 2ND FLOOR ELECTRIC CLOSET |
|
07/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK SOFFIT MAIN AREA 2. OK COFFEE BAR AREA WALLS 3. OK WALLS END OFFICE EAST SIDE 4. OK WALLS TOOL STORAGE |
|
06/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK SOFFIT @ SERVICE DRIVE 2. OK U.G TO FLOOR BOX @ CASHIER DESK 3. OK WALLS BREAK RM. TECH BATHROOM, WOMENS BATHROOM, LOCKER 4. OK HARD LIDS TECH BATHROOM, LOCKER, WOMENS BATHROOM |
|
06/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK HARD LID SERVICE DRIVE 2. OK SOFFIT @ VENDING 3. OK WALLS RMS. 166 AND HALL OUTSIDE VENDING & RM 137 |
|
06/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS, ROOM #181 |
|
06/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RMS 135-137, 149-156, 159, 164-170 |
|
04/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SERVICE INSPECTION ONLY 2. PROVIDE LETTER OF TORQUE |
|
03/28/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. POST BOND FOR TEMP POWER 2. PROVIDE LETTER OF TORQUE 3. BONDING JUMPERS NOT SIZED PROPERLY ON SERVICE RACEWAY NEC 250.102 4. INSTALL SYSTEM BONDING JUMPER @ XFMR NEC 250.30 |