Permit: T06CM05677

Parcel: 130140230


Addresses:

4220 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM05677

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/12/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G AND POLE BASES NORTHEAST PARKING LOT
11/17/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK POLE BASE BY DODGE SIGN ON COLUMBUS
2. OK U.G HR TO ABOVE POLE LIGHT
11/14/2008 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
CANCELED BY WADE
11/13/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G & POLE BASES FOR 4 POLE LIGHTS
EAST PARKING LOT TO SALES BUILDING
08/29/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK U.G TO 3RD POLE EAST LOT
2. OK POLE BASE 3RD POLE EAST LOT
08/27/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/01/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK POLE BASES WEST SIDE OF PARKING LOT EXCEPT BASES ALONG RETAINING WALL
07/30/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK FLOOR BOXES SHOWROOM AREA
2. OK U.G PVC FOR LIGHTPOLES WEST SIDE OF PARKING LOT
07/23/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G UNDER SLAB SHOWROOM AREA
04/23/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G BRANCH CIRCUITS & FEEDERS
SERVICE DEPT AND PARTS STORAGE
01/31/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK CONTINUATION OF 7 - 4" PVC TO TEP XFMR
2. INSTALL WARNING RIBBON PER NEC 300.5
01/23/2008 ELECTRIC - UNDERGROUND Partial Approval UFER APPROVED BY GLENN DABBS ON 1/22/08
3/0 FOR SERVICE
#1 FOR XFMR, #6 FOR TELEPHONE
12/14/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 9 POLE BASES SOUTH 1/2 OF LOT
12/04/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 3 - 4" PVC FROM SES 10' SOUTH FOR FUTURE
2. OK 3 - 3" PVC FROM SES 50' NORTH FOR NEXT PHASE
3. OK 1 - 3" PVC FOR XFMR AT ELECTRIC ROOM
4. OK 4" PVC FOR PHONE AT ELECTRIC ROOM
11/16/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 7 - 4" PVC FROM SES HEADING EAST TO TEP XFMR 150'
2. INSTALL WARNING RIBBON ABOVE SERVICE ENTRANCE CONDUCTORS PER NEC 300.5
11/02/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/31/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK UNDERGROUND FOR FEEDERS, BRANCH CIRCUITS, TELEPHONE FROM COLUMN LINE H TO B & 7 TO 11
2. OK UNDERGROUND FOR POLE LIGHTS SOUTH POLE LIGHTS PERIMETER & EAST POLE LIGHTS