Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 03/20/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE FILTERS IN FRESH AIR INTAKES |
|
| 03/16/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE FRESH AIR INTAKES ON A/C UNITS MAINTAIN 10' AWAY OR 2' BELOW ANY SEWER VENTS, ETC. EVERYTHING ELSE IS OK |