Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 12/18/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* - TEST NEW FITTINGS - OK TO COVER AREAS ALREADY TESTED - FOAM WRAPS |
|
| 12/14/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A MINIMUM OF 1/4" PER FOOT AND EXPOSE PIPING. 2. COPPER PIPING INSTALLED WAS NOT DEBURRED TO THE FULL ID OF THE TUBING. 3. THIS PIPING IS TO BE REMOVED AND REINSTALLED PER UPC INSTALLATION STANDARDS. ALSO, SEE NOTE #10 |