Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05657
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* NO WORK PROGRESS FINISH LAST INSPECTION |
|
03/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* COMPLETE ITEM #6 FROM INSPECTION ON 3/16/07 |
|
03/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHERE IS DISCONNECT FOR WALK IN CONDENSOR 2. SEAL RACEWAYS PER 300.7 3. CORRECTLY LABLE PANEL PER 404.8 - NO ABBREVIATIONS 4. CLEAN EXCESS FOREIGN MATERIAL FROM BOTTOM OF PANEL AND ON BREAKERS. 5. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE 6. KITCHEN RECEPTACLES TO BE GFCI PER 210.8 7. SUPPORT VDV CABLING UNDER FRONT COUNTER 8. ATTACH FIXTURES TO GRID 410.16 -- GRID IS NEW 9. SUPPORT WIRES NEEDED - 2 OPPOSITE CORNERS 10. SUPPORT FOR MC & WHIP IF USED TO BE AS PER 300.11 11. SUPPORT CEILING RECEPTACLES AS PER NOTE 12 ON PLANS. 12. NEED TO INSPECT KITCHEN EQUIPMENT FOR LABELING 13. MAINTAIN WORKING CLEARANCE AT DISCONNECTS 14. PROTECT SEAL TITE FROM SHARP METAL EDGES 15. MAINTENANCE RECEPTACLE NOT IN USABLE CONDITION OR NEEDED 16. CORRECTLY LABLE SERVICE DISCONNECTS. |