Permit: T06CM05657

Parcel: 12710084B


Addresses:

6176 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05657

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
FINISH LAST INSPECTION
03/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
COMPLETE ITEM #6 FROM INSPECTION ON 3/16/07
03/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WHERE IS DISCONNECT FOR WALK IN CONDENSOR
2. SEAL RACEWAYS PER 300.7
3. CORRECTLY LABLE PANEL PER 404.8 - NO ABBREVIATIONS
4. CLEAN EXCESS FOREIGN MATERIAL FROM BOTTOM OF PANEL AND ON BREAKERS.
5. BREAKERS TO BE LISTED FOR USE BY MANUFACTURE
6. KITCHEN RECEPTACLES TO BE GFCI PER 210.8
7. SUPPORT VDV CABLING UNDER FRONT COUNTER
8. ATTACH FIXTURES TO GRID 410.16 -- GRID IS NEW
9. SUPPORT WIRES NEEDED - 2 OPPOSITE CORNERS
10. SUPPORT FOR MC & WHIP IF USED TO BE AS PER 300.11
11. SUPPORT CEILING RECEPTACLES AS PER NOTE 12 ON PLANS.
12. NEED TO INSPECT KITCHEN EQUIPMENT FOR LABELING
13. MAINTAIN WORKING CLEARANCE AT DISCONNECTS
14. PROTECT SEAL TITE FROM SHARP METAL EDGES
15. MAINTENANCE RECEPTACLE NOT IN USABLE CONDITION OR NEEDED
16. CORRECTLY LABLE SERVICE DISCONNECTS.