Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05657
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/22/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BOND PANEL ENCLOSURE 2. PLEASE VERIFY DERATING OF CONDUCTORS PER 310.15 OK WALLS * VDV CABLEING TO BE AS PER 725.3 & 6, 800.3 & 6 |
|
01/05/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PREVENT DIELECTRIC CONTACT 2. USE APPROVED GROUNDING METHODS IN BOXES NOT BOLTS. 3. PLEASE REVISE PLANS TO REFLECT WORK DONE |
|
01/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ELECTRICAL INSPECTIONS HAVE BEEN MADE PLEASE UNCOVER WALLS COVERED WITHOUT INSPECTIONS DO NOT PROCEED |