Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM05646
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2007 | FRAMING | Approved | IVRS - Inspection :* | |
01/19/2007 | FRAMING | Partial Approval | IVRS - Inspection :* OK TO INSULATE AND DRYWALL WILL LEAVE PARTIAL TO CHECK AT FINAL THAT VENT IS STILL CORRECT. |
|
01/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAKE UP AIR INTAKE MUST BE 10' FROM SEWER VENT |
|
01/16/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS/PERMIT ON SITE |
|
01/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FRESH AIR INTAKE REQUIRES 10' CLEARANCE FROM EXHAUST 2) LINE SET INCOMPLETE 3) CONDENSATE DRAINS INCOMPLETE |