Permit: T06CM05646

Parcel: 140325130


Addresses:

3989 E ISAIAH DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM05646

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
12/12/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHIM 4 5 CO3 TRUSSES AT 3RD BEARING POINT
2) IF DAY LIGHT CAN BE SEEN BETWEEN TRIMMERS AND HEADERS, THEY NEED TO BE SHIMMED
3) RECHECK SHEAR AT GARAGE 3 + 12 ON CENTER
12/08/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL OFF FRIEZE BOARDS PER 7 DT1
2) SHIM TRIMMERS UNDER HEADERS AS NECESSARY
3) REPLACE CUT STUDS MAIN HALLWAY
4) REMOVE SHIMS FROM TRUSSES WHERE INSTALLED AT NON BEARING POINTS
5) TWO TRUSSES BEDROOM 2 NOT SUPPORTED AT BEARING POINTS. 2 NEED SHIMS
6) GARAGE SHEARWALL 7 TO BE NAILED 3 + 12 ON CENTER
12/07/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GABLE END BRACING NOT PER 6/DTI
2. GARAGE OPENING FOR SHEAR NOT PER 13/DTI MISSING STUD OR TRIMMER
3. GARAGE SHEAR WALL H.D'S NOT INSTALLED
4. NAILS BEING USED ON HOLDDOWNS HARDWARE ARE NOT 016 IN THICKNESS PER SIMPSON GUIDELINES.
5. WIND BRACE EAST WALL -- NO NAILS
6. ALL WINDBRACES NEED 2 NAILS AT BOTTOM & TOP PLATE
7. NEED RSP4 CLIP SW CORNER
8. S.W CORNER OF GARAGE SHEAR WALL NEEDS S.LID DBL STUD.
9. NEED TO SHIM ALL 3PT TRUSSES
10. EDGE BLOCKING AND NOT NAILED
11. SHEAR TRANSFER TO ROOF NOT NAILED
12. TOP PLATE SPLICE MISSING MST37 STRAP TIE PER SD2