Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM05645
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2007 | FRAMING | Approved | IVRS - Inspection :* OK TO INSULATE & DRYWALL WILL LEAVE PLUMBING PARTIAL TO INSURE NOTE REMAINS UNTIL FINAL SO THAT VENTS ARE NOT SHORTENED |
|
01/18/2007 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) ITEMS 2 AND 3 FROM 1/16/07 NOT DONE 2) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACES 3) SEAL UPPER BARRIER BY A/C 4) 4 SWITCH BOX MUST HAVE SUPPORT TWO ENDS 5) MECH AIR INTAKE MUST BE 10' FROM SEWER VENT 6) FAU FURNACE DISCONNECT MUST HAVE 30" X 30" UNOBSTRUCTED WORK AREA 7) STOPPED INSPECTION |
|
01/16/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STUCCO MESH INCOMPLETE AT BACK GABLE AND ENTRY SOFFIT 2) FIRESTOP GARAGE/ENTRY 3) INSTALL MUD RING AT UFER CLAMP 4) NO DWV TEST 5) NO POTABLE WATER TEST 6) STOPPED INSPECTION |