Permit: T06CM05645

Parcel: 140325120


Addresses:

3997 E ISAIAH DR


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM05645

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/19/2007 FRAMING Approved IVRS - Inspection :*
OK TO INSULATE & DRYWALL
WILL LEAVE PLUMBING PARTIAL TO INSURE NOTE REMAINS UNTIL FINAL SO THAT VENTS ARE NOT SHORTENED
01/18/2007 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) ITEMS 2 AND 3 FROM 1/16/07 NOT DONE
2) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACES
3) SEAL UPPER BARRIER BY A/C
4) 4 SWITCH BOX MUST HAVE SUPPORT TWO ENDS
5) MECH AIR INTAKE MUST BE 10' FROM SEWER VENT
6) FAU FURNACE DISCONNECT MUST HAVE 30" X 30" UNOBSTRUCTED WORK AREA
7) STOPPED INSPECTION
01/16/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO MESH INCOMPLETE AT BACK GABLE AND ENTRY SOFFIT
2) FIRESTOP GARAGE/ENTRY
3) INSTALL MUD RING AT UFER CLAMP
4) NO DWV TEST
5) NO POTABLE WATER TEST
6) STOPPED INSPECTION