Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM05640
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2007 | FRAMING | Approved | IVRS - Inspection :* | |
03/15/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) (8) OVER NOTCHED STUDS IN GARAGE 2) CHECK ALL OVER NOTCHED STUDS THRU-OUT 3) NOTCHES NOT TO EXCEED 25 PERCENT OF STUD DEPTH-7/8" MAX NOTCH |
|
03/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPLACE OVERNOTCHED STUD AT GARAGE-NORTH WALL 2) TRIM REBAR FOR UFER 3) BLOCK DUCT VENT 3 SIDES #4 BEDROOM CLOSET S.E. CORNER 4) FIRESTOP AROUND B-VENT CHASE 2ND FLOOR 5) HOLE IN SUB-FLOOR BEDROOM #2 6) ROCKWOOL TUBS 2ND FLOOR 7) NEED PROTECTION PLATE AT MASTER BATH TOILET BACKING. BLOCK ON 2" VENT LESS THAN 1 1/2" |