Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) SEE BLDG INSPECTOR FOR C OF O |
|
| 12/26/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REFRIDGERATION UNIT FOR ICE MACHINE NOT PIPED IN 2) ROOF JACKS NOT SEALED 3) FLUE PIPE ? WIRES NOT ANCHORED TO STRUCTURE 4) PROVIDE FEET FOR CONDENSATE LEGS 5) MAKE UP AIR NEEDS TO BE INTER LOCKED WITH EXHAUST ON HOOD 6) COMPLETE WIRING AT ANSUL CONTROL 7) NEED TO TEST HEAT SENSOR ON HOOD 8) PROVIDE BALANCE REPORT FOR HOOD AND MECHANICAL 9) PROVIDE DUCT DETECTORS ON UNITS EXCEEDING 2000 CFM PER MECHANICAL KEY NOTE 6 |