Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/18/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* THE SPECIAL CONDITION FOR THE THREE COMPARTMENT SINK IS THE SANITIZING BOWL. THAT IS THE BOWL THAT IS TO BE PIPED INDIRECT (HEALTH DEPT) THE WASH AND RINSE BOWL IS TO BE DIRECTLY CONNECTED |
|
| 12/14/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SECTION 304 - 2006 UPC EACH PLUMBING FIXTURE TO BE PROPERLY CONNECTED TO SANITARY SEWER. SECTION 801.2 - EXCLUSIONS AND CONDITIONS FOR INDIRECT WASTE - DOES NOT INCLUDE 3-COMP SINK |
|
| 12/12/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ONLY "SPECIAL" WASTE BOWL OF 3-COMP SINK TO BE INDIRECTLY WASTED. OTHER TWO COMPONENTS TO BE CONNECTED DIRECTLY TO SANITARY SEWER. 2. CUT CLEANOUTS DOWN BY ELECTRIC SERVICE PANEL 3. NEED APPROVED PLAN |