Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FUSES FOR COOLER (MUA) OVERSIZED 2. COOLER J-BOX NOT TO BLOCK ACCESS PANEL 3. SECURE EMT TO ROOF 4. SECURE ALL FLEX WITHIN 12" OF TERMINATIONS 5. PANEL DIRECTORY NOT CORRECT 6. DISCONNECTS TO HAVE PROPER FRONT CLEARANCE 7. #6 AND SMALLER GROUND TO BE GREEN - NOT TAPE ENTIRE LENGTH 8. GROUND HVAC J-BOX INSPECTION FOR KITCHEN/DINING AREA 1. ALL 120V RECEPTACLES IN KITCHEN AREA TO HAVE GFI PROTECTION 2. CLEAN UP WIRING UNDER STREAM TABLES 3. PROVIDE DISCONNECTING MEANS FOR APPLIANCES NEC 422.31 B |
|
| 12/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |