Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/28/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FUSES FOR COOLER (MUA) OVERSIZED
2. COOLER J-BOX NOT TO BLOCK ACCESS PANEL
3. SECURE EMT TO ROOF
4. SECURE ALL FLEX WITHIN 12" OF TERMINATIONS
5. PANEL DIRECTORY NOT CORRECT
6. DISCONNECTS TO HAVE PROPER FRONT CLEARANCE
7. #6 AND SMALLER GROUND TO BE GREEN - NOT TAPE ENTIRE LENGTH
8. GROUND HVAC J-BOX

INSPECTION FOR KITCHEN/DINING AREA
1. ALL 120V RECEPTACLES IN KITCHEN AREA TO HAVE GFI PROTECTION
2. CLEAN UP WIRING UNDER STREAM TABLES
3. PROVIDE DISCONNECTING MEANS FOR APPLIANCES
NEC 422.31 B
12/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*