Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/13/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/12/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/10/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SELF-TAP/SHEET METAL SCREWS NOT ALLOWED FOR GROUND BAR IN GUTTER - 250.8 2. CONDUCTORS IN GUTTER TO BE DERATED IF OVER 30 NEC 366.23 3. HAVE OVERFILLED J-BOXES (NEC 314.16) 4. MC TO BE SECURED WITHIN 12" OF TERMINATION NEC 330.30 5. SEAL INTERIOR OF RACEWAYS INTO WALK IN - NEC 300.7 6. ALL EQUIPMENT GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH - NEC 250.119 7. COMPLETE ALL LOW VOLTAGE WIRING. TO BE RAN IN A NEAT AND WORKMANLIKE MANNER, INDIVIDUALLY SUPPORTED TO STRUCTURE, NOT ON GRID OR OTHER EQUIPMENT 8. RACEWAYS TO HAVE MAX. 360 DEG. IN BENDS - NEC 358.26 9. NEED BUSHING #4 AND LARGER CONDUCTOR - NEC 300 PARTIAL INSPECTION |