Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/02/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 12/04/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK FEEDER (3) RACEWAY COVER OK POLE BASE RACEWAYS AS DISCUSSED |
|
| 10/25/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SERVICE SECONDARY RACEWAY COVER, A WARNING RIBBON MINIMUM 12" ABOVE RACEWAY WHEN YOU BACKFILL |
|
| 10/23/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* UFER NOT INSTALLED BEFORE SLAB POURED |