Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM05623
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) NO CERTIFICATIONS NEEDED OWNER/BUILDER DID ALL THE WORK |
|
08/09/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTDOOR LIGHTING NOT TO CITY CODE 2) NEED TO FINISH MECHANICAL ROOM. SHEETROCK TO PROTECT ELECTRICAL WIRING 3) MISSING EXHAUST FAN IN LAUNDRY ROOM 4) BLANK 2 RECEPTACLES AT BREAKFAST BAR 5) GFI BATHROOM NOT WORKING 6) SMOKIES NOT WORKING RIGHT 7) GFI AT KITCHEN SINK NOT ON GFI CIRCUIT 8) MISSING WALL COVER PLATE ABOVE RANGE HOOD 9) WATER SUPPLY VALVE IN MECHANICAL ROOM NEEDS TO BE FREE FOR MOVEMENT TO OPEN AND CLOSE 10) NEED TO TERMINATE CONDENSATION LINE ALL THE WAY TO GROUND LEVEL 11) SUPPORT 3/4 PVC CONDENSATION LINE ON ROOF TOP |