Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED BUBBLE COVERS ON GFI OUTLETS EAST SIDE OF HOUSE
2. SEAL METAL FLEX AT W/HEATER
3. BRACING ON SERVICE MAST NEEDS TO BE DOUBLE
08/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SERVICE NOT ENERGIZED YET
08/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SERVICE INSPECTION
1. NEED TO APPLY FOR OVERHEAD SERVICE WAIVER WITH CITY OF TUCSON (STEVE LONG)
2. SERVICE DROP TO HAVE PROPER CLEARANCE OVER ROOFS
NEC 230.24, 230.26
3. USE A LISTED MAST BRACE, NOT EMT - NEC 230.28
ALL MAST'S TO HAVE BRACE
4. SEAL FLASHINGS FOR SERVICE MASTS