Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/13/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE R5 FOIL WRAP ON ALL A/C FITTINGS 2) PROVIDE MIN 1/8" PER FT SLOPE ON CONDENSATE DRAIN 3) DUCT SMOKE DETECTORS MUST BE INSTALLED IN THE RETURN PLENIUM 4) PROVIDE AUDIBLE AND VISIBLE DRAINS |