Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM05613

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
06/13/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE R5 FOIL WRAP ON ALL A/C FITTINGS
2) PROVIDE MIN 1/8" PER FT SLOPE ON CONDENSATE DRAIN
3) DUCT SMOKE DETECTORS MUST BE INSTALLED IN THE RETURN PLENIUM
4) PROVIDE AUDIBLE AND VISIBLE DRAINS