Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM05613
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/17/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/03/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT THRU ROOF OK WATER PIPING AIR TEST OK 1. AFTER CONVERSATION WITH INSTALLER WHO HAS DONE MANY OF THESE PROJECTS BACKFLOW PROTECTION SHALL BE REQUIRED FOR WATER AT EACH CHAIR. 2. AIR PIPING ON THIS PROJECT DOES FALL UNDER THE GUIDELINES OF NFPA 99 AND IS MEDICAL AIR AND SHALL BE INSTALLED AND INSPECTED TO THAT STANDARD. |