Permit: T06CM05560

Parcel: 12307259B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/22/2007 ELECTRIC - INTERMEDIATE Approved
12/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
12/14/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT VDV CABELING IN WALLS - 725.6 & 800.6
2. SUPPORT CONDUIT DOWN WALK IN COLUMNS - NOT JUST TO EACH OTHER.
3. SECURE M/C CABLE AT 6' ON HORIZONTALS
4. RIDGELY SUPPORT BOXES TO STUDS - MC CABLES
5. TIGHTEN LOOSE FITTINGS
6. PROTECT M/C CABLE AT STUDS AND BLOCKING
ALSO, IN CHANELS
7. CONDUIT TO BE 3/4" PER PLANS
8. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE

* OLD VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6