Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 12/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
| 12/14/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT VDV CABELING IN WALLS - 725.6 & 800.6 2. SUPPORT CONDUIT DOWN WALK IN COLUMNS - NOT JUST TO EACH OTHER. 3. SECURE M/C CABLE AT 6' ON HORIZONTALS 4. RIDGELY SUPPORT BOXES TO STUDS - MC CABLES 5. TIGHTEN LOOSE FITTINGS 6. PROTECT M/C CABLE AT STUDS AND BLOCKING ALSO, IN CHANELS 7. CONDUIT TO BE 3/4" PER PLANS 8. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE * OLD VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6 |