Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. A GROUNDING ELECTRODE FOR INVERTERS IS NEEDED 2. WE HAVE UNPROTECTED CONDUCTORS PASSING THROUGH DISCONNECT -- 230.7 3. MAINTAIN WORKING CLEARANCES IN FRONT SERVICE 110.26 4. WE HAVE MULTIPLE TERMINATIONS UNDER LUG IN METER CAN. OK ROOF |