Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE HEAT STRIP CANNOT BE POWERED FROM THE 25 AMP A/C CIRCUIT. PROVIDE A SEPARATE POWER SUPPLY FOR THE HEAT STRIP OR A SINGLE DISCONNECT WITH 2 FUSE BANKS CONNECTED TO A CIRCUIT LARGE ENOUGH FOR BOTH LOADS |
|
| 03/28/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - REMOVE ALL FOIL TAPE FROM THE ROOF VENTS AND ROOF JACKS AND SEAL WITH AN APPROVED SEALANT - PROVIDE SCREEN ON TOP OF VENT PIPE FOR KITCHEN VENT - MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY - SECURE ELEC. DISCONNECT - PROVIDE 1/8" PER FT. SLOPE ON CONDENSATE DRAIN - PLANS REQUIRE A 5KW HEAT STRIP IN AC UNIT - THIS WILL REQUIRE A SEPARATE POWER SUPPLY - PLANS REQUIRE A COPPER CONDENSATE DRAIN - PLANS REQUIRE A RANGE HOOD OVER STOVE |