Permit: T06CM05548

Parcel: 111073230

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/05/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/30/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE HEAT STRIP CANNOT BE POWERED FROM THE 25 AMP
A/C CIRCUIT.
PROVIDE A SEPARATE POWER SUPPLY FOR THE HEAT STRIP OR A SINGLE DISCONNECT WITH 2 FUSE BANKS CONNECTED TO A CIRCUIT LARGE ENOUGH FOR BOTH LOADS
03/28/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- REMOVE ALL FOIL TAPE FROM THE ROOF VENTS AND ROOF JACKS AND SEAL WITH AN APPROVED SEALANT
- PROVIDE SCREEN ON TOP OF VENT PIPE FOR KITCHEN VENT
- MARK UNIT DATA PLATE WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY
- SECURE ELEC. DISCONNECT
- PROVIDE 1/8" PER FT. SLOPE ON CONDENSATE DRAIN
- PLANS REQUIRE A 5KW HEAT STRIP IN AC UNIT
- THIS WILL REQUIRE A SEPARATE POWER SUPPLY
- PLANS REQUIRE A COPPER CONDENSATE DRAIN
- PLANS REQUIRE A RANGE HOOD OVER STOVE