Permit: T06CM05548

Parcel: 111073230

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/26/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
I'LL NEED TO SEE THE TUB SET AND CONNECTED

NOTE: FURNCO NOT PERMITTED UNDER BLDG.
I'LL ALSO NEED TO SEE THE CLOSET FLANGE
08/28/2007 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1. VENT COLLAR NOT SCREWED TO WATER HEATER
2. GAS PIPING TO WATER HEATER NOT SECURE
(NOTE: ENCLOSURE IS NOT ACCEPTED METHOD OF SUPPORT)
3. REMOVE PLUG COCK ON EXTERIOR WALL
4. PROVIDE LISTING FOR SHOWER VALVE - WHICH IS NOT SECURED NOR IS THE SHOWER HEAD
5. LAVATORY DRAIN - FURNCO NOT PERMITTED - USE A SWEEP FOR THE TURNOUT

MAY NOT BE A COMPLETE LIST
07/24/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
- GAUGE REQUIRED HAS 1/10 PSI INCREMENTATIONS
- USE PIPE SUPPORTS ON GAS PIPING BELOW FLOOR, PLUMB AND SECURE RISER AT STOVE
- WH DATED 6/2005 REQUIRES PROOF OF PERMIT OR ADD WH REPLACE TO PERMIT.
- REPLACE BLACK IRON NIPPS ON WATER CONNECTIONS
TO WH
- SECURE VENT DRAFT COLLAR TO WH. SECURE VENT CONNECTOR W/GALV SCREWS
- SECURE AND SUPPORT GAS PIPING TO WH. INSTALL SEDIMENT TRAP
- ALL FIXTURES HAVE BEEN REMOVED, ALL WALL COVERINGS HAVE BEEN REMOVED
- ALL PIPE REPAIRS AND FIXTURE INSTALLATIONS REQUIRE INSPECTIONS AS NOTED ON PAGE 3 OF YOUR PLANS
- CAP OPEN DRAIN PIPES DURING CONSTRUCTION, SEWER GASSES MAY CONTAMINATE OTHER APARTMENTS.
- DO NOT COVER ANY PLUMBING PRIOR TO APPROVAL
- TUB AND LAV PIPING REQUIRES REPAIR.
- TUB VALVE SHALL BE ANTI-SCALD