Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOF 1. SEAL FLASHING - 110 2. SECURE EMT TO ROOF - 110.13 3. HEAT STRIP DISCONNECT TO HAVE PROPER FRONT WORKING CLEARANCE - 110.26 4. STRAP ALL FLEX WITHIN 12" OF TERMINATIONS - 350 INSIDE 1. BATH FAN LIGHT NOT WORKING/FAN BLADE RUBBING - 110 2. CLOSET LIGHT FIXTURES TO BE MIN. 12" AWAY FROM SHELVES - 410.8 3. HOOD FAN WITH NO WIRING? 4. PANEL DIRECTORY NOT CORRECT - 408.4 5. PROVIDE ALC FAULT PROTECTION FOR SMOKE DETECTORS -- 210.12 THERE WILL BE A REINSPECTION FEE IF ALL NOT CORRECT NEXT INSPECTION |
|
| 05/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LADDER FOR ROOF ACCESS 2. PREVIOUS CORRECTIONS NOT COMPLETED |
|
| 03/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON ROOF 1. IDENTIFY AC DATA PLATE 2. PLANS CALL FOR HEAT STRIPS 3. FUSE NOT INSTALLED INTERIOR 1. REPLACE OR REMOVE PAINTED OVER GFI IN BATHROOM 2. HAVE SHORT AT BREAKER IN LIGHTING CKT 3. BATH FIXTURES NOT FINISHED 4. OUTLETS (LIGHTING RECEPT. ETC) IN SLEEPING AREA TO HAVE ARC FAULT PROTECTION PARTIAL INSPECTION - GO THROUGH WORK BEFORE CALLING IN |
|
| 03/21/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |