Permit: T06CM05548

Parcel: 111073230

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/09/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/13/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) RE-GROUND INCOMING TELCO AND TV AT SERVICE
2) OK INTERIOR ELECTRIC COVER
3) POWER TO UNIT #1 WILL BE TURNED ON AT FINAL
11/06/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PHONE NUMBER NOT IN SERVICE - KEY NOT IN ELECTRIC BOX
UNIT LOCKED - NO ACCESS
10/29/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
NO PLANS ON SITE/CORRECTIONS NOT COMPLETED
10/02/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CALL FOR INSPECTIONS NEEDED. CANNOT DO INSPECTIONS FOR OTHER TRADES.
2. PANEL B TO BE 100 A MCB PER APPROVED PLANS
3. PROTECT/RELOCATE WIRES WITHIN 1 1/4" TO FACE OF STUD - NEC 300.4D
4. INSTALL PROTECTIVE BUSHING ON ROMEX WIRES SLEEVED NEC 300.15C THROUGH EMT
5. GROUND METAL BOX AT FRONT ENTRY NEC 250.148
6. FASTEN WIRES WITHIN 8" OF SINGLE GANG PLASTIC BOXES NEC 314.17C
7. DO NOT STAPLE ROMEX WIRES ON EDGE - NEC 334.30