Permit: T06CM05547

Parcel: 121063160

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM05547

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
DUCT BOARD MEETS ALL REQUIREMENTS
03/20/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE PROVIDE LISTING FOR DUCT BOARD USED WITH AN EVAP COOLER. IF LISTING REQUIRES APPROVAL FROM COOLER MANUFACTURER, PLEASE BE MORE SPECIFIC WITH THE LETTER FROM PHOENIX MANUFACTURING.
2. INSULATE SHEETMETAL SLEEVE ON FURNACE.
3. PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS. EXTEND VENT FROM FURNACE/WATER HEATER 2' ABOVE EVAP. COOLER.
EXTEND ANY SEWER VENTS THAT ARE CLOSER THAN 10' TO COOLER.
4. PROVIDE A ROMEX CONNECTOR ON COOLER POWER CORD.